Übersetzen...
98  H

Output disconnection detection

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet 98  H ?

A disconnection has been detected on an output terminal. This indicates a physical break in the wiring or loss of continuity to the connected output device, preventing the module from controlling the device.

Häufige Ursachen

  • Physical disconnection of an output line or cable.
  • Faulty connected load or actuator.
  • Loose or damaged terminal connection at the output module or load.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Recover the connection to the output terminal by re-securing wiring or replacing the faulty output device.

  2. 2

    After connection recovery, turn 'Alarm clear request' (Y11) on and off to clear the alarm.

  3. 3

    Verify that 'Output disconnection detection status' reads 0 (Normal) and 'Alarm flag' (X11) turns off after clearing.

Alle Codes in diesem Handbuch durchsuchen (56)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module