Übersetzen...
1401H
Input Dark Test Error
Mitsubishi Electric · MELSEC iQ-R I/O Module
Was bedeutet 1401H ?
During an input dark test, the module failed to detect the expected test pulses. This indicates a problem with the input dark test setup, the input wiring, the connected devices, or an unused input terminal that has not been correctly configured to be 'Not used'.
Häufige Ursachen
- Expected test pulses were not detected during an input dark test, possibly due to wiring or device issues.
- An unused input terminal is not correctly set to 'Not used' for 'Wiring input selection', interfering with the dark test.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
For any unused input terminals, set 'Wiring input selection' to 'Not used'.
- 2
Check for the specific input terminal with the error using Input dark test error detection state (Un\G1040).
- 3
Review and adjust the connected devices and wiring for the identified problematic input terminal.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module