Übersetzen...
E.THT

Inverter Overload shut-off (electronic overcurrent protection)

Mitsubishi Electric · A500 Inverter

Was bedeutet E.THT ?

This protective function activates to prevent damage to the inverter's output transistors. It triggers when a current exceeding 150% of the inverter's rated output current flows for an extended duration, typically if immediate overcurrent protection (for currents >200%) does not activate. The protection utilizes inverse-time characteristics, with an overload immunity of 150% for 60 seconds, leading to an inverter output stop.

Häufige Ursachen

  • Inverter output current exceeds the programmed overload limit (P1-18).
  • Overheating of the inverter power module due to insufficient cooling.
  • Abnormal load conditions on the motor causing excessive current draw.
  • Short circuit within the motor or its power leads.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the output current from the inverter (terminals U, V, W) to the motor and compare it against the inverter's rated output current.

  2. 2

    Evaluate the mechanical load on the motor for any conditions that might cause excessive current draw on the inverter, and reduce the load if necessary.

  3. 3

    Inspect the driven equipment for any signs of mechanical binding, excessive friction, or misalignment that could increase the power demand.

Alle Codes in diesem Handbuch durchsuchen (21)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric A500 Inverter