E.OHT

External thermal relay operation

Mitsubishi Electric · A500 Inverter

Was bedeutet E.OHT ?

If an external thermal relay (for motor overheat protection) or an internally mounted motor temperature relay switches on (contacts open), the inverter output is stopped. This function is activated only when the OH signal (value 7) is assigned to any of Pr. 180 to Pr. 186. The inverter requires a manual reset even if relay contacts automatically reset.

Häufige Ursachen

  • External thermal overload relay connected to the control circuit has tripped.
  • Motor winding temperature has exceeded the setting of the external thermal protector.
  • Mechanical issue causing motor to overheat and trip the relay.
  • Incorrectly sized or faulty external thermal relay.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the motor for signs of overheating; measure motor surface temperature if possible.

  2. 2

    Check the operational status of the external thermal relay or motor temperature relay (its contacts should be closed during normal operation).

  3. 3

    Verify that the value "7" (OH signal) is correctly set in one of the input terminal function selection parameters Pr. 180 to Pr. 186.

  4. 4

    Reduce the mechanical load on the motor and review its operating duty cycle.