E.LF

Output phase failure protection

Mitsubishi Electric · A500 Inverter

Was bedeutet E.LF ?

This function stops the inverter output if one of the three phases (U, V, W) on the inverter's output side (load side) results in an open phase. It can also activate if the rated motor current is extremely lower than the rated inverter current, suggesting a mismatch or very light loading conditions.

Häufige Ursachen

  • One or more phases of the output power to the motor are disconnected.
  • Internal inverter driver failure affecting one phase output.
  • Loose or broken connection at the motor terminals.
  • Faulty motor winding causing an open circuit in one phase.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the motor wiring for continuity between phases U-V, V-W, and U-W at the inverter output terminals.

  2. 2

    Inspect the motor for internal faults that could cause an open phase.

  3. 3

    Verify that the capacity of the used motor is not smaller than the inverter's capacity.

  4. 4

    Check the setting of Pr. 251 (output phase failure protection selection).

Alle Codes in diesem Handbuch durchsuchen (21)