Safety circuit fault
Mitsubishi Electric · FR E700
Was bedeutet E.SAF ?
This safety circuit fault appears when the internal safety circuit malfunctions, or when protective lines (S1-PC, S2-PC) are open. It can also be triggered by a prolonged 24V external power supply start-up time. This is a critical safety integrity issue, preventing normal operation.
Häufige Ursachen
- Safety input terminals (S1-PC, S2-PC) are open, indicating an emergency stop button pressed, safety gate open, or external safety relay tripped.
- Internal fault within the inverter's STO (Safe Torque Off) or SBC (Safe Brake Control) circuit preventing safe operation.
- External 24VDC power supply instability or dropout causing the safety circuit to lose its reference voltage for a prolonged period.
- Incorrect wiring or high resistance connection to the safety input terminals S1-PC and S2-PC from external safety devices.
- Malfunctioning safety relay (e.g., external safety monitor, programmable safety controller) failing to provide proper signal to S1-PC/S2-PC.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Verify the status of all external safety devices connected to S1-PC and S2-PC (e.g., E-stop buttons, safety interlocks, light curtains) and ensure they are all in the 'safe' or 'ready' state, providing a closed circuit.
- 2
2. Measure the voltage between S1-PC and PC, and S2-PC and PC terminals. It should be approximately 24VDC when the safety circuit is active and closed.
- 3
3. Check the stability of the external 24VDC power supply by monitoring its voltage output with an oscilloscope or a high-speed multimeter for drops below 20VDC.
- 4
4. Inspect all wiring and connections to the S1-PC and S2-PC terminals for continuity, proper termination, and absence of shorts to ground or other potentials.
- 5
5. Temporarily bypass external safety devices (only for troubleshooting, following strict safety protocols) by jumpering S1-PC to PC and S2-PC to PC. If the fault clears, the issue is external to the inverter.