Absolute value encoder initialisation error at X8
Lenze · 9300 Series
Was bedeutet Sd7 ?
The absolute value encoder at X8 has an initialisation error, is defective, or is not sending data. This may also occur if the encoder constant (C0420) for C0025=309 is altered. An uninitialised encoder can lead to uncontrolled drive movements.
Häufige Ursachen
- Absolute value encoder power supply (e.g., 24VDC) at X8 is missing or unstable, preventing the encoder from booting up.
- Communication link (e.g., SSI, EnDat, Hiperface) between the absolute encoder and X8 input is interrupted or shorted.
- Encoder constant (C0420) configured for C0025 = 309 (absolute encoder) is incorrect, causing a data interpretation error.
- Internal fault within the absolute encoder, preventing it from initializing or sending valid position data.
- Loose or corroded connections at the X8 terminal block or the encoder's motor-mounted connector.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Power off the drive, disconnect the encoder cable from X8, and measure the encoder power supply voltage at the X8 terminals with power on.
- 2
Inspect the absolute encoder cable for physical damage, continuity, and correct pinout for the specific communication protocol (e.g., SSI clock/data).
- 3
Verify parameter C0025 is set to 309 for absolute encoder, and C0420 (encoder constant) matches the encoder's specified resolution/turns.
- 4
Check the encoder's diagnostic LEDs (if present) for any fault indications during power-up or operation.
- 5
Ensure the encoder is properly mechanically mounted and aligned, as some absolute encoders require correct initial physical positioning.
- 6
Cycle power to the encoder and drive in sequence, then initiate an encoder re-initialization routine via the drive's keypad or software.