CE1

CAN1_IN communication error

Lenze · 9300 Series

Was bedeutet CE1 ?

The CAN1_IN object is receiving faulty data or communication is interrupted. This is likely caused by wiring issues at X4, a faulty sender, or an insufficient monitoring time for the communication, leading to unreliable data exchange.

Häufige Ursachen

  • CAN1_IN communication bus failure between devices.
  • Faulty CAN transceiver on connected devices.
  • Wiring issue on the CAN1_IN bus (shorts, opens).
  • Termination resistor issues on the CAN1_IN bus.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check wiring at X4 for proper connections and integrity.

  2. 2

    Check the sender device for correct operation and data transmission.

  3. 3

    Increase monitoring time under C0357/1, if necessary, to account for communication delays.

  4. 4

    Switch off monitoring by setting C0591 = 3.