Sd2
Lenze · 9300 Series
Was bedeutet 082 ?
A resolver error has occurred at terminal X7, typically indicating an interrupted resolver cable. This prevents accurate position feedback.
Häufige Ursachen
- Break or open circuit in one or more conductors of the resolver feedback cable connected to terminal X7.
- Poor or corroded connection at the resolver connector, terminal X7 on the drive, or within the resolver itself.
- Damaged resolver sensor (e.g., mechanical impact, contamination, internal short) providing incorrect or no feedback signals.
- Incorrect resolver wiring to terminal X7 (e.g., swapped sine/cosine signals, incorrect shield connection).
- Excessive electrical noise or interference on the resolver cable causing signal corruption.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Power down and lockout the drive. Disconnect the resolver cable from terminal X7 on the drive and at the resolver end.
- 2
2. Using a multimeter, check continuity of each individual wire within the resolver cable from end to end.
- 3
3. Measure the resistance of the resolver windings at the resolver connector (e.g., between reference and sine, reference and cosine). Refer to the resolver datasheet for expected values.
- 4
4. Inspect terminal X7 on the drive and the resolver connector for bent pins, corrosion, or loose connections.
- 5
5. Ensure the resolver cable shield is properly connected to the drive's designated ground terminal and the motor frame.