Übersetzen...
OH51

Motor Overtemperature (PTC Warning)

Lenze · 8200 Series

Was bedeutet OH51 ?

The motor's PTC thermistor has detected an overtemperature condition, triggering a WARNING (not a TRIP). This typically occurs when the motor operates under impermissible high currents or frequent/long acceleration processes, or if the PTC sensor is not connected while monitoring is active (C0119 = 2 or 5). While a warning, continued operation can still lead to motor damage if the condition escalates.

Häufige Ursachen

  • Prolonged motor operation at currents exceeding its nominal rating (P5-01, P5-02).
  • Insufficient cooling of the motor due to blocked fan, dirty cooling fins, or high ambient temperature.
  • Inadequate motor sizing for the application, leading to continuous overloading.
  • Incorrect motor thermal model parameters (e.g., P6-10 to P6-13) configured in the drive, leading to underestimation of heating.
  • Faulty PTC thermistor or wiring to the drive's PTC input (e.g., terminals X1/X2), causing erroneous temperature readings.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Monitor the actual motor current (U0-01) and compare it against the motor's nominal current (P5-01) and drive's nominal current (P2-01).

  2. 2

    Inspect the motor's cooling fan for proper operation and clean any dust or debris from the motor's cooling fins.

  3. 3

    Measure the ambient temperature around the motor and ensure it is within the motor's specified operating limits.

  4. 4

    Review and adjust motor thermal model parameters (P6-10 to P6-13) in the drive controller to match the motor's thermal characteristics more accurately.

  5. 5

    Disconnect the PTC thermistor wires from the drive (terminals X1/X2), measure the resistance across the thermistor; it should be below ~1.6 kOhm at ambient and increase significantly with temperature.

Alle Codes in diesem Handbuch durchsuchen (40)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes