OC3

Controller Overload (Acceleration)

Lenze · 8200 Series

Was bedeutet OC3 ?

The controller has experienced an overload condition during acceleration, possibly due to an acceleration time (C0012) that is too short, an improperly dimensioned drive, or issues with the motor/cabling like a defective motor cable or interturn fault. Persistent overloading can lead to drive component degradation and premature failure.

Häufige Ursachen

  • Acceleration time (Parameter C0012) is set too short for the load's inertia, requiring excessive current.
  • Drive is undersized for the peak current demand during acceleration.
  • Excessive mechanical load or sudden load increase during acceleration.
  • Motor parameter (e.g., P0-01, P0-02) mismatch leading to inefficient motor control.
  • Motor current limits (e.g., P1-54, P1-55) configured incorrectly or set too high relative to drive capacity.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Increase the acceleration time by adjusting Parameter C0012 (e.g., from 3.0s to 5.0s) to reduce acceleration current.

  2. 2

    2. Monitor the actual motor current (e.g., via display parameter C0004) during acceleration and compare it against the drive's nominal output current.

  3. 3

    3. Verify that the drive's nominal current rating matches or exceeds the continuous and peak current requirements of the application.

  4. 4

    4. Check for any mechanical binding or excessive friction in the driven machinery that could increase acceleration load.

  5. 5

    5. Verify that motor data parameters (P0-01 to P0-05) are accurately entered for the connected motor.