Übersetzen...
LU

Mains undervoltage

Lenze · 4800/4900 Series

Was bedeutet LU ?

This fault indicates that the incoming mains voltage has dropped below the permissible operating threshold for the drive. By default, this condition is configured as a Warning, meaning it alerts the operator and is entered into the history buffer, but it does not immediately inhibit pulses. Continued operation under undervoltage can lead to reduced motor performance or potential damage if not resolved promptly.

Häufige Ursachen

  • Utility grid voltage sag or brownout conditions affecting the facility's power supply.
  • Overloaded electrical circuit within the plant, causing excessive voltage drop across cables and transformers.
  • Incorrectly set undervoltage trip threshold parameter (e.g., P0-12) in the drive, causing premature warning/trip.
  • Loose or corroded connections on the incoming mains supply lines to the drive's input terminals (L1, L2, L3).
  • Faulty isolation transformer or line reactor connected upstream of the drive, causing excessive voltage drop under load.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the actual incoming mains voltage (line-to-line) at the drive's input terminals (L1, L2, L3) using a true RMS multimeter; compare to the drive's rated voltage (e.g., 400V).

  2. 2

    Check the drive's undervoltage trip threshold parameter (e.g., P0-12) and adjust if it is set too high (e.g., typically 340V for a 400V system).

  3. 3

    Inspect all power connections from the main distribution panel to the drive's input terminals for looseness or corrosion; torque to manufacturer's specification.

  4. 4

    Monitor the mains voltage over time using a power quality analyzer to detect intermittent sags or prolonged low voltage conditions.

  5. 5

    Verify the sizing and condition of any upstream transformers or line reactors; check for excessive voltage drop across them under load.

Alle Codes in diesem Handbuch durchsuchen (31)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Lenze LU — Instandsetzung: Mains undervoltage technische An… | ErrorLib