PS1 Off

Power Supply 1 (Short Battery Backup) Not Present / Drive Bus Off

Kuka · Sunrise Cabinet Med Controller

Was bedeutet PS1 Off ?

The PS1 Voltage Green LED is OFF, indicating either that Power Supply 1 (with short battery backup) is not present or that the drive bus is in a 'BusPowerOff' state. This condition could prevent motor drives from receiving power, resulting in a loss of motion control.

Häufige Ursachen

  • Power Supply 1 (PS1), potentially for short battery backup, is offline.
  • Failure or disconnection of the PS1 unit.
  • The drive bus voltage is too low or absent.
  • Battery backup for PS1 has failed or is disconnected.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the infeed at connector X1, verifying the presence and stability of the rated voltage of 27.1 V.