Übersetzen...
26132

Collective brake fault, KPP/KSP (axis)

Kuka · KR C4 Controller

Was bedeutet 26132 ?

This fault is signaled by the brake cable monitoring device, indicating a short-circuit, overloading, or a break in the brake connection affecting all axes. This is a critical safety fault, as it affects the ability to hold the robot axes.

Häufige Ursachen

  • Short-circuit in the brake cable
  • Overcurrent condition in the brake circuit
  • Break in the brake cable connection
  • No brake connected (if expected)

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the brake voltage for all axes.

  2. 2

    Measure the motor and brake for proper resistance and continuity.

  3. 3

    Inspect the brake cable and motor cable for physical damage, shorts, or breaks.

  4. 4

    Reinitialize the drive bus by cycling Power Off / Power On.

  5. 5

    Check the KSP module.

Alle Codes in diesem Handbuch durchsuchen (21)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes