OC1-Trip (Overcurrent)
Kuka · KR C2 Robot Controller
Was bedeutet 11 ?
This fault indicates an overcurrent condition. For the KPS-600, it specifically signifies an I*t overload of the brake resistor during the charging phase, implying excessive energy dissipation. For KSDs, it means a power unit overcurrent, typically a short-circuit or ground fault detected by hardware monitoring, which is a critical fault risking damage to the power stage.
Häufige Ursachen
- OC1-Trip: Overcurrent detected, phase 1 (P1-01).
- Sudden load increase exceeding motor capacity.
- Short circuit in motor winding or power cable.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the insulation resistance between motor phases U-V, V-W, U-W using a megger at 500VDC — expect >1 MΩ.
- 2
Measure motor current on each phase during operation and compare to motor nameplate Full Load Amperage (FLA).
- 3
Verify that motor parameters (e.g., nominal current, overload limits) stored in the drive match the motor nameplate.
- 4
Inspect the brake resistor for physical damage or signs of overheating, and measure its resistance value.