0106
Inverter not OK
Kone · V3F25/18 drive
Was bedeutet 0106 ?
The V3F25/18 drive is prevented from operating until this fault is corrected. This indicates a general issue with the inverter's internal operation or its external control signals and feedback.
Häufige Ursachen
- Loose or incorrect connections of the tachometer and thermal switch (XM2).
- The value for Tacho fault counter (6_35) parameter may be too sensitive.
- LBR LED does not light.
- LBR lights but LBE is not activated at start (check parameter 6_38).
- MLB is 'shutdown' (check voltage in supply and X10/16 in MLB for +24V).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check connections of tachometer and thermal switch (XM2).
- 2
If Tacho fault counter (6_35) parameter is too sensitive, turn the elevator to RDF and back to Normal to reset it.
- 3
If LBR LED does not light, refer to AS-11.65.008 and circuit diagrams.
- 4
If LBR lights but LBE is not activated at start, check parameter (6_38).
- 5
If MLB is 'shutdown', check voltage in the supply and at terminals X10/16 in MLB (+24V).
- 6
Remove the U REF2 jumper.