Fuse Broken Off

Kone · Frequency Inverter

Was bedeutet 5 ?

This error indicates that a protective fuse within the drive or its associated power circuit has blown. A blown fuse typically points to an overcurrent condition or a short circuit occurring either upstream or downstream of the fuse.

Häufige Ursachen

  • Short circuit in the motor winding or the motor cable.
  • Overcurrent condition caused by motor overload or an internal drive malfunction.
  • Input power supply surge or transient voltage event.
  • Internal component failure within the drive creating a short circuit path.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify and replace the blown fuse with one of the exact specified type and rating.

  2. 2

    Before replacing the fuse, measure the insulation resistance of motor windings and cables (phase-to-phase and phase-to-ground) using a megger to detect any short circuits.

  3. 3

    Check for any direct shorts or persistent overcurrent conditions in the load or wiring that could have caused the fuse to blow.

  4. 4

    Verify the input power supply for stable voltage and the absence of damaging surges or transients.