25

Anti-slippage Operation Time Limit Exceeded

Kone · Frequency Inverter

Was bedeutet 25 ?

This error occurs when the lift fails to receive any leveling signal within the specified time limit defined by parameter F62. The default time limit is 32 seconds, with a configurable range between 20 and 45 seconds according to GB7588-2003. A prolonged absence of leveling signals indicates a failure in position detection during car movement, potentially due to slippage.

Häufige Ursachen

  • The lift fails to receive a leveling signal within the time set by parameter F62.
  • Actual slippage of the car, where the measured slippage distance error exceeds 5mm.
  • Incorrect car decoration weight or an unbalanced load affecting the balance coefficient.
  • Malfunctioning or misaligned leveling switches or plates.
  • Overshoot in the speed regulator preventing proper leveling.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the value of parameter F62 (Time limit for anti-slippage operation); ensure it is within the 20-45 second range and appropriately set for the application.

  2. 2

    Inspect and adjust the position of leveling switches and plates if the leveling deviation exceeds 15mm.

  3. 3

    Review and verify the car's current balance coefficient, especially if car decoration has been completed or modified, and adjust if necessary.

  4. 4

    For high-speed elevators experiencing persistent slippage, consider installing an encoder at the governor side for main-board position feedback.

  5. 5

    Adjust parameter F24 to 2 (Analog with creep) or 0 (Multi-speed operation) to absorb slippage errors by creeping.

  6. 6

    Check the leveling insert plate length consistency; the flashboard on the second floor is the benchmark for other floors, ensuring they are identical.

Alle Codes in diesem Handbuch durchsuchen (37)