Übersetzen...
RS 07

RS Para # Too Big

Indramat · ServoDyn D Servo Drive

Was bedeutet RS 07 ?

This serial communication error is a specific instance of "RS Para # Wrong", indicating that the parameter number transmitted to the CLM01.3-M is greater than 99. The CLM01.3-M expects parameter numbers to be in the range of 00 to 99.

Häufige Ursachen

  • The parameter number in the serial command is greater than 99.
  • Typographical error in the parameter number during transmission, e.g., an accidental extra digit.
  • Sending device software error, attempting to access a non-existent parameter number.
  • Using an incorrect parameter list for the CLM01.3-M, leading to attempts to access out-of-range parameters.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify that the parameter number being transmitted is between 00 and 99. Refer to Chapter 7 (Serial Interface) for the correct parameter format.

  2. 2

    Correct the parameter number in the transmitted serial command to be within the valid range.

  3. 3

    Check the serial communication link for data corruption or unusual characters.

  4. 4

    Re-transmit the parameter command after verifying the parameter number.

  5. 5

    Ensure the sending device's software uses the correct parameter map for the CLM01.3-M.

Alle Codes in diesem Handbuch durchsuchen (51)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Indramat ServoDyn D Servo Drive