Übersetzen...
RS 04

RS Checksum Error

Indramat · ServoDyn D Servo Drive

Was bedeutet RS 04 ?

This serial communication error occurs when the checksum calculated by the CLM01.3-M from received data does not match the checksum transmitted by the sending device. This indicates data corruption during transmission, if checksum is enabled.

Häufige Ursachen

  • Data corruption or loss during serial transmission between the sending device and the CLM01.3-M.
  • Checksum calculation error on the sending device, resulting in an incorrect transmitted checksum.
  • Parameter 81 (Serial Interface Functions) is configured incorrectly for checksum (e.g., checksum enabled on one side, disabled on the other).
  • Noise or interference on the serial communication line.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify that the checksum being transmitted by the sending device is calculated correctly as per Chapter 7 (Serial Interface).

  2. 2

    Ensure that Parameter 81 (Serial Interface Functions) on the CLM01.3-M is configured to match the checksum setting (enabled/disabled) of the sending device.

  3. 3

    Re-transmit the information after confirming checksum calculation and settings.

  4. 4

    Inspect the serial communication cable for damage, proper shielding, and correct connections.

  5. 5

    If possible, use diagnostic tools to monitor the serial data stream and verify checksum integrity at different points in the communication path.

Alle Codes in diesem Handbuch durchsuchen (51)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Indramat ServoDyn D Servo Drive
Indramat RS 04 Support: RS Checksum Error Analyse | ErrorLib