Parameters Lost
Indramat · ServoDyn D Servo Drive
Was bedeutet 29 ?
This error occurs when the CLM01.3-M's back-up battery, responsible for retaining parameters when power is off, is disconnected or has low voltage. This results in the loss of critical configuration parameters, indicated by asterisks (*) on the display.
Häufige Ursachen
- The lithium back-up battery (on the MOK 11 card) is disconnected, depleted, or has low voltage.
- Parameters were not re-entered or restored after a battery replacement or power loss.
- The MOK 11 card (Memory and Battery Module) is faulty or improperly seated.
- Firmware replacement or update without proper parameter backup/restore procedure.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Turn OFF power to the CLM01.3-M.
- 2
Remove the MOK 11 card (Memory and Battery Module) as shown in Figure 2.3 of the manual.
- 3
Replace the 3.6-volt lithium back-up battery on the MOK 11 card.
- 4
After replacing the battery, turn power ON and re-enter all necessary CLM01.3-M parameters, as they will have been lost (refer to Chapter 4).
- 5
Verify that all CLM01.3-M parameters are stored with valid numbers (no asterisks) and correspond to the application's requirements.