Immediate Stop
Indramat · ServoDyn D Servo Drive
Was bedeutet 13 ?
This error occurs when the +24 Vdc signal is applied to the CLM01.3-M's Immediate Stop input (connector X3, pin 5). This input is designed to command an immediate halt to machine operation for safety purposes.
Häufige Ursachen
- The Immediate Stop pushbutton on the machine has been pressed, activating the input.
- Faulty wiring or a short circuit is causing a continuous +24 Vdc signal to be present at connector X3, pin 5.
- A malfunctioning Immediate Stop pushbutton is physically stuck or electrically shorted.
- External control logic or device inadvertently activating the Immediate Stop input.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify that the Immediate Stop pushbutton is not currently pressed or stuck in an actuated position.
- 2
Consult the machine builder's wiring diagrams to understand how the Immediate Stop input (X3, pin 5) is integrated into the flying cutoff system.
- 3
Check the wiring at CLM01.3-M connector X3, pin 5 for any loose connections, shorts to +24 Vdc, or damage.
- 4
Inspect the Immediate Stop pushbutton for mechanical damage or wear that could cause it to stick.
- 5
If external control is involved, verify the output signal from the controlling device that feeds the Immediate Stop input.