Maximum braking time exceeded
Indramat · Indradrive
Was bedeutet F6024 ?
The drive has exceeded the maximum allowable braking time during a deceleration sequence. This means the motor or load took too long to come to a stop or reduce its speed, often indicating an issue with the braking system or excessive inertia.
Häufige Ursachen
- Insufficient braking torque or worn mechanical brakes.
- Excessive inertia of the load relative to the drive's braking capacity.
- Incorrectly configured deceleration ramp or braking parameters (e.g., S-0-0078 Ramp Time Neg).
- Faulty braking resistor or chopper circuit.
- External forces or continuous regenerative load.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the mechanical brakes (if present) for proper function and wear, ensuring they provide adequate braking torque.
- 2
Verify the drive's deceleration ramp parameters (e.g., S-0-0078 Ramp Time Neg) are set appropriately for the application's inertia.
- 3
Ensure the braking resistor is correctly sized and connected, and its chopper circuit within the drive is functioning.
- 4
Inspect the mechanical system for any binding or high friction that would prolong deceleration.
- 5
If applicable, verify that there are no external forces or continuous regenerative loads hindering deceleration.