Übersetzen...
F8000

Fatal hardware error

Indramat · IndraDrive MPx02

Was bedeutet F8000 ?

"F8000" is a collective diagnostic message for underlying fatal hardware errors within the IndraDrive MPx02, specifically F8060 (Overcurrent in power section) and F8069 (+/-15Volt DC error). This code is typically not displayed directly, as the more specific fault is shown. The occurrence of this error leads to an immediate torque-free shutdown of the drive, making operation impossible.

Häufige Ursachen

  • Underlying fatal hardware issues such as overcurrent in the power section.
  • An error in the internal +/-15VDC power supply (F8069).
  • Internal hardware fault within the IndraDrive MPx02 control or power section.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the drive display for subsequent specific fatal error messages like F8060 or F8069, which provide more direct fault information.

  2. 2

    Use the service channel to read parameters S-0-0390 (Diagnostic message number) and S-0-0095 (Diagnostic message) to identify the precise hardware fault.

  3. 3

    Perform a complete power cycle of the IndraDrive MPx02 by switching off the main supply, waiting for discharge, and then re-applying power.

  4. 4

    If F8060 (Overcurrent) is indicated, inspect the motor, motor cables, and power section for short circuits or ground faults.

  5. 5

    If F8069 (+/-15VDC error) is indicated, this points to an internal drive hardware fault and requires contacting Indramat service.

Alle Codes in diesem Handbuch durchsuchen (56)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes