Undervoltage Error
Indramat · ECODRIVE Controller
Was bedeutet F226 ?
The drive controller monitors the DC bus voltage. If the DC bus voltage falls below a predefined minimal threshold, the drive independently shuts down, triggering the configured error reaction. This protects the drive from operation with insufficient power.
Häufige Ursachen
- The power source has been interrupted without first switching off the drive enable (RF) signal.
- Disturbance or sag in the main power supply.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the logic and sequence of operations for the drive enable (RF) signal within the connected control system, ensuring it is removed before the power source is interrupted.
- 2
Check the main power supply voltage to the drive controller for stability and correct levels.
- 3
Measure the DC bus voltage during operation to identify any sags or interruptions.
- 4
Ensure the control enable signal is removed to clear the error.