Control voltage supply fault power supply unit (HVE only)
Indramat · CLM01.3-M Flying Cutoff Control
Was bedeutet E387 ?
This fault applies only to the Indramat HVE power supply unit. It indicates that the incoming power voltage supply exceeds the permissible tolerance range of 3x 380-480V, ± 10%, which can lead to unstable operation or damage to the unit.
Häufige Ursachen
- Mains voltage supply (line voltage) is outside the specified tolerance range (e.g., below 342V or above 528V for 380-480V nominal).
- A main fuse in the control cabinet supplying the HVE unit has blown or is damaged.
- Loose or corroded connections in the mains power supply circuit to the HVE.
- Malfunction of the HVE's internal voltage monitoring circuit.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the incoming three-phase mains voltage at the input terminals of the Indramat HVE power supply unit to verify it is within 380-480V, ± 10%.
- 2
Check the mains fuses in the control cabinet that supply power to the HVE unit for continuity and proper rating, and replace if necessary.
- 3
Inspect all power wiring connections to the HVE unit for tightness and corrosion.
- 4
Verify that the upstream power supply and distribution system are stable and providing correct voltage.