Übersetzen...
F273

Error power supply E-Stop

Indramat · DIAX 04

Was bedeutet F273 ?

The DIAX04 SSE-03VRS drive's power supply for the Emergency-Stop (E-Stop) circuit has an error. This signifies that the voltage supply for the E-Stop monitoring is faulty or an overload/short circuit is detected. This is a critical safety fault, as the E-Stop function cannot be guaranteed, requiring immediate shutdown to ensure personnel and machine safety.

Häufige Ursachen

  • Short circuit or overload on the E-Stop circuit power supply output.
  • Damage to the wiring connected to the DIAX04 SSE-03VRS E-Stop input circuit.
  • Faulty E-Stop button or external safety relay drawing excessive current or internally shorted.
  • Internal fault within the DIAX04 SSE-03VRS drive's power supply circuit for safety inputs.
  • Loss of 24VDC control voltage feeding the DIAX04 SSE-03VRS safety input section.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect all E-Stop related wiring from the DIAX04 SSE-03VRS drive's safety input. If the fault clears, the issue is external.

  2. 2

    Measure the voltage at the E-Stop circuit power supply output terminals on the DIAX04 SSE-03VRS. Verify it's within specification (e.g., 24VDC).

  3. 3

    Check the E-Stop wiring for shorts to ground or power, and for continuity. Inspect E-Stop buttons and safety relays for proper function.

  4. 4

    Isolate external safety components one by one to identify the faulty device or wiring section.

  5. 5

    If the fault persists even with external wiring disconnected, there may be an internal fault with the DIAX04 SSE-03VRS drive's safety input power supply circuit.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes