231-A006

SPLC-CC%2: Cross comparison failed, output %4

Heidenhain · TNC CNC Controllers

Was bedeutet 231-A006 ?

This error indicates a failure in the cross-comparison of SPLC-CC outputs. It occurs when the Safety PLC (SPLC) program of the CC[x] defines an output as 0 (LOW), but the value read from the terminal for that output is 1 (HIGH), suggesting a discrepancy between commanded and actual output states.

Häufige Ursachen

  • Error in the cross comparison of the SPLC-CC outputs.
  • SPLC program of the CC[x] defines the output as LOW (0), but the terminal value is HIGH (1).
  • Incorrect wiring of the output, potentially causing it to be pulled HIGH.
  • SPLC program logic issue where output signals do not remain stable for at least 2 SPLC cycles.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the physical wiring of the faulty output (indicated by %4) for any short circuits, external voltage sources, or incorrect connections.

  2. 2

    Review the SPLC program logic for the affected output to ensure signals for setting and resetting the output remain stable for a minimum of 2 SPLC cycles.

  3. 3

    Verify the output module's functionality and its ability to correctly switch between LOW and HIGH states.

  4. 4

    Measure the voltage at the output terminal to confirm the actual state when commanded LOW and HIGH by the SPLC.

Alle Codes in diesem Handbuch durchsuchen (47)