Fronius Solar Energy

60 Fehlercodes dokumentiert

1

Hardware fault

This fault indicates a general internal hardware malfunction within the device. This type of fault typically implies a component failure or significant internal system anomaly, preventing normal operation.

2

EEROM fault

An EEROM (Electrically Erasable Read-Only Memory) fault indicates an issue with the non-volatile memory used for storing configuration or operational data. This can lead to incorrect settings or failure to store critical operational parameters, potentially affecting system stability.

3

Internal memory error

This fault signifies an error within the device's internal memory system. This could be related to RAM or other internal storage, impacting program execution and data processing, potentially leading to system instability or crashes.

4

Fieldbus hardware fault

This fault indicates a hardware problem with the fieldbus communication interface. This affects the device's ability to communicate over the fieldbus network, preventing data exchange with other connected systems or controllers.

5

Script error

A script error indicates an issue during the execution of an internal script or programmed sequence within the device. This could be due to corrupted script data, programming logic errors, or unexpected operational conditions preventing the script from running correctly.

7

RS transmission buffer overflow

This error occurs when the transmit buffer for the RS communication interface (likely RS-232/485) receives more data than it can process or hold. This can lead to data loss during transmission and disruption of serial communication.

102

AC voltage too high

The AC voltage from the public grid is detected as excessively high. The inverter temporarily disconnects from the grid and will resume feeding energy once grid conditions return to the permissible range.

103

AC voltage too low

The AC voltage from the public grid is detected as too low. The inverter temporarily disconnects from the grid and will resume feeding energy once grid conditions return to the permissible range.

105

AC frequency too high

The AC grid frequency is detected as excessively high. The inverter temporarily disconnects from the grid according to safety standards and will resume operation once the frequency returns to the permissible range.

106

AC frequency too low

The AC grid frequency is detected as too low. The inverter temporarily disconnects from the grid according to safety standards and will resume operation once the frequency returns to the permissible range.

107

No AC grid

No AC grid connection is detected by the inverter. This prevents the inverter from feeding energy into the grid.

108

Stand-alone operation detected

The inverter has detected an unintentional stand-alone operation (island mode), meaning it is operating independently from the main grid. This is typically a safety mechanism to prevent unsynchronized grid reconnection.

143

Emergency power overload

The emergency power mode has detected an overload and has been interrupted. The inverter will attempt to restart emergency power mode up to three times. If these attempts are unsuccessful, status code 145 will be displayed.

144

Emergency power short-circuit

A short-circuit has been detected in the emergency power circuit. This will interrupt emergency power mode and prevent its operation.

145

Status code 143 or 144 has occurred more than three times

This status code indicates that either an emergency power overload (143) or an emergency power short-circuit (144) has occurred more than three times. This points to a persistent issue with the emergency power circuit that requires attention.

303

DC module overtemperature (PV)

An overtemperature condition has been detected in the DC module associated with the PV system. This causes a short-term interruption in grid feed-in as the inverter attempts to restart its operation.

306

Not enough PV power or no battery power requested

There is insufficient PV power available for feeding energy into the grid, and simultaneously, no power has been requested from the battery. This results in a short-term interruption while the inverter repeats its start-up routine. This is often displayed routinely early morning or evening due to low insolation and may not indicate a fault.

307

DC low (PV input voltage too low)

The DC input voltage from the PV system is too low for feeding energy into the grid. This causes a short-term interruption as the inverter repeats its start-up routine. This is often displayed routinely early morning or evening due to low insolation and may not indicate a fault.

313

Battery input voltage too high

The battery input voltage has exceeded its permissible limits, leading to a short-term interruption of energy feeding into the grid. The inverter will attempt to restart its routine, and this code can occur sporadically without a persistent fault.

324

DC module overtemperature (battery)

An overtemperature condition has been detected in the DC module associated with the battery. This causes a short-term interruption in grid feed-in as the inverter attempts to restart its operation.

417

Hardware ID problem

An issue with the hardware identification within the inverter has been detected. The inverter will attempt to reconnect and resume grid feed-in automatically.

431

Software problem

An internal software problem has occurred within the inverter, preventing it from feeding any energy into the grid.

432

Software problem

An internal software problem has occurred within the inverter, preventing it from feeding any energy into the grid.

436

Functional incompatibility (PC boards)

One or more PC boards in the inverter are incompatible, possibly after a replacement. The inverter will attempt to automatically reconnect and resume grid feed-in.

438

Functional incompatibility (PC boards)

One or more PC boards in the inverter are incompatible, possibly after a replacement. The inverter will attempt to automatically reconnect and resume grid feed-in.

445

Compatibility error / Invalid power stage set configuration

This code indicates either a compatibility error, such as after a PC board replacement, or an invalid configuration of the power stage set. This prevents the inverter from feeding energy into the grid.

457

Grid relay is sticking or neutral conductor ground voltage too high

The inverter is unable to feed energy into the grid due to either a sticking grid relay or an excessively high neutral conductor ground voltage. The neutral conductor ground voltage must be less than 30V for safe operation.

480

Functional incompatibility (PC boards)

This fault indicates that one or more PC boards in the inverter are not compatible with each other, often due to a replacement of a PC board. This prevents the inverter from feeding energy into the grid.

481

Functional incompatibility (PC boards)

This fault indicates that one or more PC boards in the inverter are not compatible with each other, often due to a replacement of a PC board. This prevents the inverter from feeding energy into the grid.

482

Setup interrupted after initial start-up

The initial start-up setup process of the inverter was interrupted, preventing the inverter from feeding any energy into the grid.

484

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

485

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

486

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

487

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

488

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

489

CAN transmit buffer is full

The CAN (Controller Area Network) transmit buffer within the inverter is full, indicating a communication bottleneck or issue. This prevents the inverter from feeding energy into the grid.

509

No energy fed into the grid in the past 24 hours

This warning message indicates that no energy has been fed into the grid by the inverter during the last 24-hour period. This can occur if conditions for grid feed-in are not met, preventing the system from operating as expected.

517

Power derating caused by excessively high temperatures

When the inverter's internal temperature becomes excessively high, it initiates power derating to protect components, displaying a warning message. The system automatically reduces output power until temperatures return to a safe range.

520

No energy fed into the grid by the PV in the past 24 hours

This warning message indicates that the photovoltaic (PV) system has not fed any energy into the grid over the last 24 hours. This typically suggests an issue with PV production or grid connection conditions.

558

Functional incompatibility (PC boards)

This warning indicates that one or more PC boards within the inverter are not compatible with each other. This often occurs after a PC board has been replaced with an incorrect or non-matching version.

559

Functional incompatibility (PC boards)

This warning indicates that one or more PC boards within the inverter are not compatible with each other. This often occurs after a PC board has been replaced with an incorrect or non-matching version.

601

CAN bus is full

The CAN (Controller Area Network) bus transmit buffer is full, indicating a communication issue within the inverter. This prevents the inverter from feeding any energy into the grid.

608

Functional incompatibility (PC boards)

One or more PC boards in the inverter are not compatible with each other, for example, after a PC board has been replaced. This prevents the inverter from feeding any energy into the grid.

721

EEPROM has been re-initialised

The EEPROM (Electrically Erasable Programmable Read-Only Memory) has been re-initialised, possibly due to a reset or an internal event. A warning message is shown on the display.

746

Error occurred during update process

An error occurred during a software update process, causing the update to be interrupted and a warning message to be displayed.

751

Time lost

The inverter's internal clock has lost its time setting, resulting in inaccurate timestamps. A warning message is shown on the display.

753

Internal error: Real Time Clock module is in emergency mode

The Real Time Clock (RTC) module is operating in emergency mode. This may lead to inaccurate or lost time data, although feeding energy into the grid typically continues normally.

758

Internal error: Real Time Clock module is in emergency mode

The Real Time Clock (RTC) module is operating in emergency mode. This may lead to inaccurate or lost time data, although feeding energy into the grid typically continues normally.

775

PMC power stage set not available

The PMC (Power Management Controller) power stage set is not available, resulting in a warning message on the display.

975

Software on device is inconsistent

The software installed on the device is inconsistent or corrupted, preventing the inverter from feeding any energy into the grid.

976

Unregistered battery module detected

A battery module is connected but has not been registered or activated, making battery operation impossible. Grid feed-in will resume.

978

Communication error between Fronius Symo Hybrid and Fronius Solar Battery

A communication error exists between the Fronius Symo Hybrid inverter and the Fronius Solar Battery. This prevents battery operation, but grid feed-in will resume.

979

Communication error between Fronius Symo Hybrid and Fronius Solar Battery

A communication error exists between the Fronius Symo Hybrid inverter and the Fronius Solar Battery. Battery operation is not possible, and grid feed-in resumes. This code is displayed if not in standby mode.

980

No communication between Fronius Symo Hybrid and Fronius Solar Battery

There is no communication detected between the Fronius Symo Hybrid inverter and the Fronius Solar Battery. This prevents battery operation, but grid feed-in will resume.

983

Communication error between battery controller and battery modules

A communication error exists within the Fronius Solar Battery system, specifically between its internal battery controller and the individual battery modules. This prevents battery operation, but grid feed-in resumes.

984

Battery controller has stopped Charge mode

The battery controller has stopped its charge mode, preventing battery operation. Grid feed-in will resume.

986

Overtemperature at Fronius Solar Battery

The Fronius Solar Battery has tripped due to an overtemperature condition. Battery operation is no longer possible, but grid feed-in resumes.

987

Undertemperature at Fronius Solar Battery

The Fronius Solar Battery has tripped due to an undertemperature condition. Battery operation is no longer possible, but grid feed-in resumes.

988

Communication error between Fronius Symo Hybrid and Fronius Smart Meter

A communication error exists between the Fronius Symo Hybrid inverter and the Fronius Smart Meter. This results in no meter data being available, preventing battery operation, but grid feed-in resumes.

989

No communication with Fronius Smart Meter

This code indicates a lack of communication between the Fronius Symo Hybrid inverter and the Fronius Smart Meter, resulting in no meter data and inability to perform battery operation. Feed-in to the grid will resume, but battery functionality is impaired.