503

Overcurrent on DC side (PV2)

Fronius · Primo GEN24

Was bedeutet 503 ?

The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing from the PV2 string on the DC side. This suggests a potential short circuit within the PV2 array or an improper string configuration.

Häufige Ursachen

  • Overcurrent on the DC side (PV2).
  • Short circuit on the PV array.
  • Incorrect PV array sizing or configuration.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect the PV2 string using the DC disconnector and visually inspect all PV modules, wiring, and connectors for any damage or indications of a short circuit.

  2. 2

    Measure the open-circuit voltage (Voc) and short-circuit current (Isc) of the PV2 string and compare them against expected values from the module datasheet.

  3. 3

    Confirm that the PV2 string configuration (number of modules in series and parallel) adheres to the Fronius Primo GEN24 208-240 inverter's maximum DC current specifications.

  4. 4

    Inspect any external DC combiner box or array wiring associated with PV2 for potential short circuit conditions.

  5. 5

    If external components are confirmed good, the fault might be internal to the inverter; contact Fronius service.