303
DC module overtemperature
Fronius · Primo GEN24 Operating Instructions
Was bedeutet 303 ?
This code indicates that the DC module within the inverter has reached an excessively high temperature. This leads to a short-term interruption in energy feeding, after which the inverter will resume its startup routine once temperatures normalize.
Häufige Ursachen
- Insufficient cooling due to blocked cooling air openings or a dirty heat sink.
- High ambient temperatures exceeding the inverter's operating limits.
- Internal fan malfunction or failure.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Clean and purge all cooling air openings and the heat sink of the inverter to ensure proper airflow.
- 2
Verify that the inverter's installation location allows for adequate ventilation and is not exposed to excessive heat sources.
- 3
Inspect internal cooling fans for proper operation and any obstructions.