Übersetzen...
7

DC Link Overvoltage (PSM, PSMR)

Fanuc · Series 30i CNC

Was bedeutet 7 ?

The DC voltage at the main circuit DC link is abnormally high. This typically occurs due to excessive regenerated power that the PSM cannot dissipate, or issues with the AC power source's output impedance. An overvoltage condition risks damage to DC link components and connected modules.

Häufige Ursachen

  • Excessive regenerated power, indicating the PSM does not have sufficient capacity
  • The output impedance of the AC power source is too high
  • Main circuit power supply was switched off with an emergency stop state released

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the specification of the PSM to ensure its capacity is sufficient for regenerated power loads

  2. 2

    Check the AC power source output impedance; expect the voltage variation at maximum output time to be within 7%

  3. 3

    Check the sequence of operations, especially regarding power supply switching in conjunction with emergency stop states

Alle Codes in diesem Handbuch durchsuchen (20)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes