Main Circuit Capacitor Recharge Failure (PSM, PSMR)

Fanuc · Series 30i CNC

Was bedeutet 5 ?

The main circuit capacitor within the PSM or PSMR unit failed to recharge within the specified time. This can indicate an issue with the power supply capability, a short circuit in the DC link, or a component failure in the recharge circuit. Failure to recharge can prevent the unit from powering up or operating correctly.

Häufige Ursachen

  • Too many SVM and/or SPM units connected, exceeding the PSM specification
  • The DC link is short-circuited
  • The recharge current limiting resistor is defective

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the specification of the PSM for the total number and type of connected SVM/SPM units

  2. 2

    Check the DC link connection for any signs of a short circuit

  3. 3

    Replace the distributing board to address a potentially defective recharge current limiting resistor

Alle Codes in diesem Handbuch durchsuchen (20)