Übersetzen...
11

Motor thermistor over temperature

Danfoss · VLT Micro Drive FC 51

Was bedeutet 11 ?

The motor's thermistor input indicates an over-temperature condition, or the thermistor or its connection is disconnected. This provides direct thermal protection for the motor, signaling a critical overheating risk if not addressed.

Häufige Ursachen

  • Motor operating under sustained heavy load or with insufficient cooling (e.g., blocked fan, high ambient temperature).
  • Motor thermistor (PTC or NTC type) open-circuited due to broken wire or internal failure.
  • Thermistor wiring disconnected from the drive's input terminals (e.g., X3:1, X3:2) or poorly crimped connection.
  • Thermistor input short-circuited (e.g., wiring pinched) causing an erroneous low resistance reading.
  • Incorrect thermistor type selected in drive parameters (e.g., P3-05 set to wrong sensor type).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the resistance of the motor thermistor directly at the motor terminals using an ohmmeter (e.g., 250 Ohms to 1.5 kOhms for PTC at room temp).

  2. 2

    Verify continuity of the thermistor wiring from the motor to the drive's dedicated thermistor input terminals (e.g., X3:1, X3:2).

  3. 3

    Check the motor's operating current (P0-03) and motor surface temperature with an infrared thermometer to confirm actual thermal state.

  4. 4

    Ensure the thermistor input parameter (P3-05) is correctly configured for the connected sensor type (e.g., PTC, KTY, NTC).

  5. 5

    Inspect the motor cooling fan for proper operation and clean any debris from motor cooling fins.

Alle Codes in diesem Handbuch durchsuchen (51)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes