Übersetzen...
ALARM 12

Torque limit

Danfoss · VLT HVAC Drive High Power

Was bedeutet ALARM 12 ?

The motor's torque has exceeded the value set in parameter 4-16 Torque Limit Motor Mode or the generator torque limit in parameter 4-17 Torque Limit Generator Mode. This condition can be a warning or escalate to an alarm and trip, protecting the mechanical system from excessive stress.

Häufige Ursachen

  • Mechanical obstruction or jamming in the driven machinery, causing the motor to demand excessive torque.
  • Process material buildup or blockage, increasing the load on the motor.
  • Torque limit settings (P4-16, P4-17) are set too low for the application's actual torque requirements.
  • Ramp times (acceleration P3-41, deceleration P3-42) are set too short, causing high transient torque demands.
  • Incorrect motor data parameters, leading to inaccurate torque calculation by the frequency converter.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Monitor the motor torque (parameter 16-15 Motor Torque) on the frequency converter display during operation.

  2. 2

    Inspect the mechanical system for any obstructions, jamming, or excessive friction that would increase load.

  3. 3

    Increase the torque limit values in P4-16 (Torque Limit Motor Mode) and P4-17 (Torque Limit Generator Mode) gradually, if the mechanical system allows.

  4. 4

    Increase acceleration ramp time (P3-41 for ramp 1) to reduce peak torque during startup.

  5. 5

    Verify motor nameplate data (kW, V, A, Hz, RPM) against the frequency converter's motor setup parameters (P1-03 to P1-07).

  6. 6

    Check for proper mechanical alignment of shafts, couplings, and bearings.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Danfoss VLT HVAC Drive High Power