38.1316

Internal Fault: Option software in slot B not supported

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 38.1316 ?

The software on the option card installed in slot B is not recognized or supported by the frequency converter's firmware. This indicates a fundamental incompatibility, preventing the option card from integrating correctly with the drive's control system.

Häufige Ursachen

  • Installation of an option card in slot B with unsupported or incompatible software (e.g., beta firmware, custom modification).
  • The drive's main firmware version is too old to recognize or interface with the software on the installed option card.
  • Corruption of the option card's firmware, rendering it unreadable or unrecognizable by the main drive.
  • Attempting to use an option card from a different product series or manufacturer that is physically installed but logically incompatible.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Record the exact model number and part number of the option card installed in slot B.

  2. 2

    2. Verify the frequency converter's main firmware version via the LCP (parameter 15-00) or manufacturer software.

  3. 3

    3. Refer to the manufacturer's compatibility matrix or documentation to confirm that the option card's software is officially supported by the drive's current firmware version.

  4. 4

    4. If compatibility is confirmed, attempt to re-flash the option card's firmware with the latest officially supported version using manufacturer software.

  5. 5

    5. If incompatibility is identified, replace the option card in slot B with a supported model, or update the main drive firmware if the option card is newer and requires it for compatibility.