Übersetzen...
38.0
Internal Fault: Serial port initialization error
Danfoss · VLT HVAC Drive FC 102
Was bedeutet 38.0 ?
The internal serial communication port failed to initialize upon power-up or during operation. This can prevent communication with the LCP or external serial devices, indicating a possible internal hardware or firmware issue with the control board.
Häufige Ursachen
- Local Control Panel (LCP) connection issues; LCP cable is damaged or not fully seated.
- Faulty LCP module preventing proper communication with the drive's control board.
- Internal serial communication hardware (UART chip) on the control board has failed.
- Severe EMI interfering with the internal serial communication lines during initialization.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Power down the drive, then remove and firmly re-seat the LCP on its connector.
- 2
2. Attempt to operate the drive with a different, known-good LCP, if available, to rule out LCP module failure.
- 3
3. Visually inspect the LCP connector on the control board for bent pins or signs of damage.
- 4
4. If the fault persists, replacement of the control board is likely required due to internal serial port hardware failure.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Danfoss VLT HVAC Drive FC 102