Übersetzen...
18

Start Failed

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 18 ?

The drive attempted to start the motor but failed to achieve successful operation. This could be due to mechanical issues, incorrect motor parameters, insufficient power, or an inability to overcome the initial load.

Häufige Ursachen

  • Excessive mechanical load or binding on the motor shaft or driven equipment, preventing successful startup.
  • Incorrect motor parameters (e.g., P7-01, Motor Rated Current; P7-02, Motor Rated Speed) entered into the drive, leading to improper control.
  • Drive acceleration ramp time (P3-02, Ramp 1 Accel Time) set too short for a high-inertia load, causing overcurrent during acceleration.
  • Motor not correctly wired for the drive's output voltage (e.g., star/delta configuration mismatch).
  • Insufficient drive output current (e.g., P6-02, Rated Motor Current) capacity for the required starting torque of the motor.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Disconnect the motor from its mechanical load and attempt to start the motor unloaded to determine if the fault is mechanical or electrical.

  2. 2

    2. Verify that all motor nameplate data (e.g., P7-01, Motor Rated Current; P7-02, Motor Rated Speed; P7-03, Motor Rated Voltage) is accurately programmed into the drive.

  3. 3

    3. Monitor the drive's output current (P0-01, Motor Current) during a start attempt and compare it to the drive's overcurrent trip limit.

  4. 4

    4. Increase the acceleration ramp time (P3-02, Ramp 1 Accel Time) to reduce the current demand during startup for applications with high inertia.

  5. 5

    5. Manually rotate the motor shaft and driven equipment to check for mechanical binding, seized bearings, or other obstructions.

Alle Codes in diesem Handbuch durchsuchen (75)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes