Fire Mode Limits Exceeded
Danfoss · VLT HVAC Basic FC 101
Was bedeutet WARNING 202 ?
While in Fire Mode, one or more warranty-voiding alarms have been suppressed, indicating that the drive is operating under extreme conditions beyond its normal limits. This significantly increases the risk of equipment damage and voids the product warranty.
Häufige Ursachen
- Prolonged motor overload (e.g., actual motor current exceeding 150% of nominal) without the drive tripping, due to Fire Mode suppression.
- Excessive internal inverter temperature (e.g., heatsink temperature above 95°C) maintained for extended periods without thermal protection trips.
- Sustained operation at extreme DC link voltage levels (e.g., significantly above or below nominal) that would typically trigger undervoltage or overvoltage alarms.
- Motor forced to operate continuously outside its safe speed envelope, for example, running far above nominal speed, due to Fire Mode overriding speed limits.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Monitor actual motor output current (e.g., Parameter P0-03 'Output Current') and compare against the motor nominal current (P1-22) to identify prolonged overload conditions.
- 2
Check the drive's internal heatsink temperature (e.g., Parameter P0-05 'Heatsink Temp') and ensure that ambient ventilation around the drive enclosure is not obstructed.
- 3
Measure incoming line voltage at the drive input terminals (L1, L2, L3) and the DC link voltage (P0-01) during operation to identify extreme voltage conditions.
- 4
Inspect the motor for any physical signs of overheating (e.g., discolored paint, burnt smell) or unusual noise that indicates mechanical stress.
- 5
After safely exiting Fire Mode, conduct a comprehensive inspection of the motor, drive, and driven mechanical equipment for any damage resulting from extreme operating conditions.