Übersetzen...
ALARM 70

Illegal power section configuration

Danfoss · VLT HVAC Basic FC 101

Was bedeutet ALARM 70 ?

The control card and power card installed in the frequency converter are incompatible with each other. This prevents the drive from starting or operating correctly, requiring compatible hardware components for functionality.

Häufige Ursachen

  • Control card from one drive family or power range installed into a power card from a different family/range.
  • Control card and power card revision numbers are mismatched or not approved for combination by the manufacturer.
  • Incorrect replacement parts used during maintenance or repair, leading to incompatibility.
  • Internal communication fault between the control card and power card during startup or operation.
  • Damaged communication ribbon cable or connectors between the two sections of the drive.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the part numbers and revision levels of both the control card and the power card against the drive's bill of materials or compatibility list.

  2. 2

    Ensure that the control card is fully seated and properly connected to the power card's interface.

  3. 3

    Inspect the ribbon cable or communication bus connector between the control and power sections for damage or loose contacts.

  4. 4

    Attempt to re-seat the control card firmly onto the power card interface.

  5. 5

    If mismatched, replace either the control card or power card with a compatible unit from the same series and rating.

Alle Codes in diesem Handbuch durchsuchen (40)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes