Motor phase W missing
Danfoss · VLT HVAC Basic FC 101
Was bedeutet ALARM 32 ?
The motor phase W connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.
Häufige Ursachen
- Loose or disconnected conductor at the drive output terminal W.
- Loose or disconnected conductor at the motor terminal W.
- Break or high resistance in the motor cable's W phase conductor.
- Faulty contactor or circuit breaker in the motor output circuit (if present) for phase W.
- Failure of the drive's output power stage (e.g., IGBT) specifically for phase W.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Power off the drive and disconnect input power. Visually inspect and tighten connections for the W-phase motor cable at both the drive's W output terminal and the motor's W terminal.
- 2
Measure the resistance of the W-phase motor cable conductor from the drive end to the motor end to check for continuity (expect < 1 Ohm).
- 3
With motor cables disconnected from the drive, measure the resistance between motor terminals W-U, W-V, and U-V. All three values should be balanced and low.
- 4
Check for any external fusing or contactors in the W-phase motor circuit for continuity and proper operation.
- 5
If cable and motor are verified good, the fault indicates a potential internal drive hardware issue with the W-phase output.