Control word timeout
Danfoss · VLT AutomationDrive FC 301/302
Was bedeutet 17 ?
No communication is detected from the control word source to the frequency converter. This warning is active only when parameter 8-04 Control Word Timeout Function is not set to [0] Off. If set to [5] Stop and trip, the drive will ramp down to a stop and issue an alarm.
Häufige Ursachen
- Communication interruption from the master controller (e.g., PLC, HMI) to the drive via fieldbus (e.g., Profibus, Ethernet/IP).
- Incorrect fieldbus communication settings (e.g., baud rate, address, timeout period P8-04) between the drive and the master.
- Faulty fieldbus cable (e.g., broken conductor, improper shielding) preventing data transmission.
- Master controller stopped sending control words or entered an error state.
- Drive's fieldbus option card malfunction or incorrect installation preventing proper communication.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the fieldbus communication status on the master controller (PLC/HMI) and ensure it is sending data packets or control words.
- 2
Inspect the fieldbus cable for proper connection, damage, and correct termination resistors at both ends of the segment.
- 3
Check parameter 8-04 (Control Word Timeout Function) and 8-05 (Control Word Timeout Time) settings; adjust timeout time (e.g., increase from 1.5s to 3s) if network latency is high.
- 4
Monitor the status of the fieldbus option card LEDs (e.g., green/red) for communication activity and errors.
- 5
Perform a network diagnostic test (e.g., ping for Ethernet/IP, bus status for Profibus) from a connected device to verify connectivity.