Option software in slot B too old
Danfoss · VLT AutomationDrive FC 301/302
Was bedeutet 1300 ?
The software installed on the option card in slot B is outdated. This can lead to compatibility problems, missing functionalities, or unstable operation with the main drive software.
Häufige Ursachen
- The option card's firmware in Slot B has not been updated to match the requirements of the drive's recently updated main firmware.
- An older option card was installed into a drive with a newer main firmware without performing the necessary option firmware update.
- The drive's main firmware includes a compatibility check that flags option cards with firmware below a minimum required version.
- Previous attempt to update the option card firmware in Slot B failed or was incomplete.
- Corrupted firmware file used during a failed update attempt for the option card in Slot B.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Identify the installed option card in Slot B and determine its current firmware version via the drive's LCP (e.g., P15-06).
- 2
2. Verify the compatibility matrix (e.g., from manufacturer website) for the drive's main firmware (P15-05) and the required option card firmware in Slot B.
- 3
3. Download the correct, updated firmware file for the option card in Slot B from the manufacturer's support portal.
- 4
4. Perform the firmware update procedure for the option card in Slot B using the designated software tool (e.g., MCT 10, USB-to-RS485 adapter) or SD card.
- 5
5. After updating, perform a power cycle of the drive and verify the new firmware version is correctly reported (e.g., P15-06).