Emergency-Stop
Bosch Rexroth · IndraDrive MPx02
Was bedeutet F4034 ?
This fault indicates that an emergency stop condition has been detected and activated on the IndraDrive MPx02, leading to an immediate and controlled shutdown of the drive. The E-stop signal is typically a hardwired input that overrides normal operation for safety.
Häufige Ursachen
- Activation of an external emergency stop push button or safety device.
- Break in the emergency stop circuit wiring, leading to loss of the safety signal.
- Faulty emergency stop contactor or relay in the safety circuit.
- Incorrect wiring or configuration of the emergency stop input terminals on the IndraDrive MPx02.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect all emergency stop buttons and safety interlocks in the machine or system to ensure none are pressed or active.
- 2
Verify the integrity of the emergency stop safety circuit, checking for loose connections, damaged cables, or open contacts.
- 3
Measure the voltage at the emergency stop input terminals of the IndraDrive MPx02 to confirm the expected safe state (e.g., 24VDC present for active state).
- 4
Bypass the external E-stop circuit temporarily (if safe to do so for troubleshooting) to determine if the fault originates from the external wiring or an internal drive issue.
- 5
Check safety parameters related to the E-stop function in the IndraDrive MPx02 for correct configuration.