Dynamization time interval incorrect
Bosch Rexroth · IndraDrive MPx02
Was bedeutet F3134 ?
This non-fatal safety error indicates that the configured or monitored time interval for dynamization of safety-related signals is incorrect or outside permissible limits on the IndraDrive MPx02. Dynamization is a testing method for safety inputs/outputs to detect faults like short circuits to power or ground, by periodically switching them.
Häufige Ursachen
- Incorrect parameterization of the dynamization time interval (e.g., S-0-0083, S-0-0084).
- Discrepancy between the expected and actual dynamization timing of safety signals.
- External safety device (e.g., light curtain, safety gate) responding too slowly or too quickly.
- Internal safety hardware fault affecting time measurement or signal generation for dynamization.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Review and adjust the dynamization time interval parameters (e.g., S-0-0083 'Monitored test pulse width 1', S-0-0084 'Monitored test pulse width 2') in the IndraDrive MPx02 to match the requirements of the connected safety devices.
- 2
Verify the response times of external safety devices connected to dynamized inputs/outputs.
- 3
Inspect the wiring of dynamized safety signals for proper connections and minimal impedance, ensuring clean signal transmission.
- 4
Check for sources of electromagnetic interference that might corrupt the timing of the dynamization pulses.
- 5
If the issue persists, consider isolating the specific safety input/output causing the error and testing its response directly.