Übersetzen...
F2190

Incorrect Ethernet configuration

Bosch Rexroth · IndraDrive MPx02

Was bedeutet F2190 ?

The Ethernet network configuration of the drive is incorrect or incompatible. This fault indicates that the drive cannot properly establish or maintain communication over its Ethernet interface, affecting control, monitoring, and data exchange with other network devices. This will prevent network-based operation.

Häufige Ursachen

  • Incorrect IP address, subnet mask, or gateway settings
  • Duplicate IP address on the network
  • Mismatch in Ethernet protocol settings (e.g., EtherCAT, PROFINET)
  • Faulty Ethernet cable or connection
  • Network switch configuration issues

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the Ethernet cable connecting the IndraDrive MPx02 to the network switch or controller for damage, proper seating, and correct cabling type.

  2. 2

    Check the status LEDs on the drive's Ethernet port and the corresponding port on the network switch for link activity and data transfer indications.

  3. 3

    Verify the drive's Ethernet network parameters (IP address, Subnet Mask, Gateway, device name/ID) in the IndraWorks software or drive HMI against the system's network design specifications.

  4. 4

    Verify the corresponding Ethernet network configuration (e.g., IP address of the drive in the PLC's hardware configuration) on the primary controller (PLC/NC) to ensure it matches the drive's settings.

  5. 5

    Check network reachability by attempting to ping the drive's assigned IP address from a connected computer or the network controller.

Alle Codes in diesem Handbuch durchsuchen (99)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes