Übersetzen...
F2177

Modulo limitation error of motor encoder

Bosch Rexroth · IndraDrive MPx02

Was bedeutet F2177 ?

A modulo limitation error has occurred with the motor encoder. This typically indicates that the encoder's position value has exceeded or fallen below its configured modulo range, or that an unexpected wrap-around occurred. This suggests an issue with encoder scaling, position tracking, or data integrity within the modulo calculation.

Häufige Ursachen

  • Incorrect modulo parameters configured for the motor encoder
  • Encoder counting issues or skipped pulses
  • Rapid, uncommanded movement exceeding modulo range limits
  • Software error in modulo position calculation
  • Noise causing erroneous encoder readings

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify configured encoder parameters, specifically the modulo value (e.g., S-0-0027) and encoder resolution (e.g., P-0-0098), within the IndraDrive configuration software (IndraWorks) against the motor and application specifications.

  2. 2

    Inspect the motor encoder cable for any signs of damage, wear, or loose connections at both the motor and IndraDrive ends, ensuring proper shielding is intact.

  3. 3

    Measure the encoder supply voltage at the IndraDrive feedback connector (e.g., X2 or X3) to confirm it aligns with the encoder's specified operating voltage range.

  4. 4

    Monitor the actual position value (S-0-0000) and modulo actual position value in the IndraDrive diagnostic software while slowly jogging the axis, looking for erratic readings, sudden jumps, or values exceeding the configured modulo limit.

Alle Codes in diesem Handbuch durchsuchen (99)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes