Übersetzen...
F2176

Loss of measuring encoder reference

Bosch Rexroth · IndraDrive MPx02

Was bedeutet F2176 ?

The drive has lost the reference signal from the measuring encoder. This encoder is often used for high-precision position measurement, distinct from the motor's primary encoder. Loss of its reference means the system cannot accurately track or control the position of the monitored component, impacting measurement and control accuracy.

Häufige Ursachen

  • Damaged measuring encoder cable or connector
  • Defective measuring encoder hardware
  • Severe electrical noise interfering with measuring encoder signals
  • Loose measuring encoder mounting
  • Incorrect parameter configuration for the measuring encoder

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the measuring encoder cable for any signs of physical damage, cuts, or crushed sections, and ensure all connectors are securely fastened at both the encoder and the drive.

  2. 2

    Verify the supply voltage provided to the measuring encoder against the specified voltage in the encoder's datasheet or the drive's wiring diagram.

  3. 3

    Check the shielding and grounding of the measuring encoder cable for proper termination and continuity to minimize electromagnetic interference.

  4. 4

    Verify the drive parameters configured for the measuring encoder, such as encoder type, resolution, and scaling, match the installed hardware and application requirements.

Alle Codes in diesem Handbuch durchsuchen (99)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes