xxxx 0101

Watchdog Time Elapsed

Beckhoff · TwinSAFE Logic FB

Was bedeutet xxxx 0101 ?

The FSoE watchdog timer on a device has expired, meaning that a safety telegram was not received within the configured watchdog period. This indicates a communication timeout, potentially due to network delays, device malfunction, or disconnection, leading to a safe state.

Häufige Ursachen

  • Watchdog timer expired, indicating system unresponsiveness.
  • The control processor is not executing code within the expected timeframe.
  • Software hang or deadlock.
  • Excessive system load causing delays.
  • Hardware issue preventing regular task execution.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the physical network connection (Ethernet cables, connectors) to ensure continuity and reliability.

  2. 2

    Verify the FSoE watchdog time parameter is appropriately set for the network latency and device cycle times.

  3. 3

    Monitor network load and traffic to identify any bottlenecks or excessive delays that could cause timeouts.

  4. 4

    Inspect the FSoE master and slave devices for operational status, power supply issues, or internal errors that could prevent telegram transmission.