43

Phase UW Short

Allen-Bradley · PowerFlex 700

Was bedeutet 43 ?

Excessive current has been detected between output terminals U and W. This indicates a short circuit condition between these two motor phases or their connecting wiring, leading to very high currents and potential drive damage.

Häufige Ursachen

  • Short circuit detected between Phase U and Phase W.
  • Damaged insulation between Phase U and Phase W motor windings.
  • Faulty motor power cable with U and W shorted.
  • Internal short circuit in the drive's output stage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the motor and drive output terminal wiring for a shorted condition between U and W.

  2. 2

    Replace the drive if wiring and motor are verified good.